Aerial Infrared Roof Moisture Surveys
Gregory R. Stockton, Stockton Infrared Thermographic
Services
Posted 2-21-05
Back to Preventive maintenance articles
INTRODUCTION
IR P/PM (infrared predictive/preventive maintenance)
is not limited to annual infrared surveys of electrical switchgear.
For instance, infrared thermography can be a very effective
tool for roof asset management. IR roof moisture surveys are
performed on roofs to quantify the extent of roof moisture
(water) that is inside the roof system. Infrared thermography
is not leak management. No matter how the water got into the
substrate, the purpose of this type of survey is simply to
find and document where the water is located. Extending the
life of a roof will save the owner the expense and aggravation
of re-roofing or re-covering. Re-roofing means that the roof
is taken down to the decking and replaced completely. Re-covering
means that the waterproofing layer(s) are removed, the wet
insulation is removed and replaced and a new waterproofing
layer is put down. The cost of an infrared roof moisture survey
is three to five CENTS per square foot. It cost between three
and five DOLLARS per square foot to repair/replace roofs, so
knowing the exact location of the subsurface water is extremely
useful information, since only those areas that are damaged
need to be repaired. This information is used to plan budgets
and when needed, as a bid document for contracting repairs
and/or replacement of the roof.
ROOF MAINTENANCE IN GENERAL
The ravages of sun, wind, rain,
snow, chemicals, leakage, rapid changes in temperature and
time - will eventually cause
every roof to fail. Some roofs last 40-50 years…when
they are well-maintained. Owners may believe that a roof warranty
will somehow protect them from having to do maintenance. Not
so, as roof warranties are written by roofing manufacturers
for the purpose of protecting themselves from liability. For
example, often a warranty is written so that if improperly
installed or defective roofing materials are used on a roof
and water leaks into the electrical switchgear room causing
an explosion, the roofing manufacturer will replace the materials,
the roofer will reinstall the materials, but the building owner
has to pay for the replacement of the switchgear and any downtime
that resulted from the failure. Also, the roofer’s and
roofing manufacturer’s liability, in the case of roof
failures are also reduced by vaguely written roof warranties,
which do not define words like "regular" or "routine" maintenance.
Not accepting the roof warranty is not the answer, since the
roof will not be installed unless the owner agrees to the warranty.
To eliminate these problems, the building owner should have
an agreement with a qualified roofer or roof consultant to
inspect and maintain the roof (in accordance with the terms
of the warranty) at least once a year.
Waterproofing problems manifest themselves in two ways: Leakage
and entrained moisture contamination. Leakage is pretty simple,
although the leak inside the building rarely directly relates
to the exact spot on the roof, since the water flows down the
slope of the roof to a spot that is not sealed and into the
building at that point. Most leaks occur where the waterproofing
is sealed or where there is a penetration of the roof. Since
most types of roof systems absorb some amount of water, it
is harder to find the exact spot of water contamination in
the insulation because it may not leak into the building until
it has absorbed all the water it can hold. There are three
types of surveys that are used to find water in a roof. Nuclear
gauges-which count neutrons, capacitance meters-which measure
resistance, and infrared-which measures heat. Both nuclear
gauges and capacitance meters are used to take spot readings
on a 10' X 10' or 20' X 20' grid on the roof. These measurements
are used to extrapolate where the water is from the readings
obtained from the gauge. They are good for types of roofs that
do not gain or lose much solar energy and therefore, do not
lend themselves to infrared.
BASICS OF INFRARED ROOF MOISTURE
SURVEYS
During the day, the sun radiates energy onto the roof
and into the roof substrate, and then at night, the roof radiates
the heat back into outer space (See Figure 1). This is called
radiational cooling. Areas of the roof that are of a higher
mass (wet) retain this heat longer than that of the lower mass
(dry) areas. Infrared imagers can detect this heat and "see" the
warmer, higher mass areas, during the "window" of
uneven heat dissipation.

Figure 1) Areas of the roof that are wet retain heat longer
than dry areas.
Some roofs and insulation types or combinations do not absorb
any water. These roofs leak straight into the building. Even
roofs which have insulation types that do absorb water, some
do not exhibit a good infrared signal, primarily for two reasons.
1) The surface is too reflective, and/or 2) the roof’s
ballast is so thick (or dense), that daylight radiation is
not absorbed into the substrate (insulation), therefore it
cannot be emitted back into the atmosphere at night. Even with
a strong infrared signal, factors on the roof can affect the
analysis and interpretation of the data. Some of these factors:
water between multiple layers, old patches, heavy flood coats,
reflective coatings, heat-producing equipment under the roof –or
heat blowing down onto the roof, stains, ponding water on the
roof, heavy build-up of ballast at parapet walls and along
edges, etc. These roofs should be inspected by other methods
as described above.
WALK-ON INFRARED ROOF SURVEYING
To perform a walk-on or on-roof
survey properly, a crew of three to four people is needed:
an experienced infrared thermographer
and helper, an experienced roof consultant or roofer and the
building owners' representative for access and security. The
crew walks around the roof(s) and when an area of suspect moisture
is found, the roof consultant verifies it is wet and then the
helper marks the edges of the area directly on the roof with
marking paint as instructed by the thermographer. The crew
needs authorization and access to all areas and levels of the
roof(s) from either ladders or roof hatches and plenty of time
to collect data. The infrared images are stored on videotape
or digital media and printed (See Figure 2).

Figure 2) On-roof IR image.
The next
day, the thermographer goes back on the roof(s) to take matching
visual photographs of the marked areas that contain
subsurface moisture. The problem with on-roof infrared is
that when one is standing on the roof, eye-level is at best
six
feet over the surface. Even with the best hand-held infrared
camera available, there is virtually no way to get large
areas (800 sq. ft. blobs or 100’ long striations) of moisture
contamination on the screen in one infrared shot. Taking multiple
shots is labor-intensive and makes the report confusing. When
performing on-roof surveys, many times “you can’t
see the forest for the trees.” Marking the roof is
fairly easy, but it is very difficult/time-consuming to produce
accurate
drawings of the wet areas from painted lines on a roof. Often
the drawing supplied by the owner is outdated, incorrect
or even non-existent.
AERIAL INFRARED ROOF SURVEYING
There is never a time when on-roof
imagery is better than aerial imagery. While the best IR imagery
of a roof is taken
from the air, the same laws of physics apply to both aerial
IR and on-roof IR…like a dry roof, low winds and no rain
on the night of the survey. Also, the "window" when
the roof is radiating heat differently from wet and dry areas
is longer with aerial infrared because slight nuances of temperatures
over large areas are distinguishable. The high angle of view
allows the aerial thermographer to produce more usable imagery
and therefore accurate CAD drawings. The cameras that are used
for on-roof surveys are not of sufficient spatial resolution
to obtain good imagery from flight altitudes of 1,200 – 1,500
feet above the roof, so high-resolution, large format IR cameras
(See Figure 3) are required.

Figure 3) Large format infrared imager, fixed-mounted in a
light aircraft.
Once the aircraft is over a building, very little
time (five minutes per 200,000 square feet, about 25 minutes
for two million
square feet) is required to fly over making multiple passes.
The imagery is recorded on digital videotape. Visual photographs
are taken earlier in the day or the next day. After returning
to the office, the photos are printed and the thermographs
are saved on the computer. The raw video imagery, thermographs
and photographs are used to make an edited videotape copy
of the passes over the building. Both visual and infrared images
are used to do the analysis by overlaying the CAD drawing
of
the roof ‘over’ the digitized photographs and thermographs.
The drawings always need to be corrected, because rooftop equipment
has been removed, moved or added since the last update of the
drawings. Then, areas of suspected moisture contamination are
drawn on the CAD file. The result is a report where visual,
infrared and CAD components (printed and video) are well matched
and lined-up. The report is given to a roof consultant who
verifies the wet insulation during the day, while making other
condition notes on the roof.
Fixed-wing aerial infrared imaging provides many advantages
over on-roof infrared imaging:
- Access to multiple levels of the roof is not a problem.
- High-angle, straight down infrared images lessen reflection
problems.
- High-resolution images capture large areas at once, making
report writing easier and less expensive to produce.
- Plan-view imaging allows for infrared images, visual images
and AutoCAD drawings to be reconciled closely. As
a result, the report is clear, concise and easy to understand
(See Figure
4a, 4b, 4c).
- Plan view imaging allows accurate marking of areas of
suspect roof moisture contamination.
- The printed CAD drawings can be used on the roof to paint
areas of moisture contamination directly on the roof (after
verification),
if desired.

Figure 4a) Photograph of a roof.

Figure 4b) Thermograph of a roof.

Figure 4c) Scaled CAD drawing of a roof.
- The aerial infrared thermographer can wait for a
good night for imaging, surveying many roofs under good conditions.
- The trending of roof moisture becomes possible.
- An aircrew of two can easily survey many millions of square
feet in a single night.
- Processing the data is done in the office, not on the roof.
- Report components can be purchased as needed. Aerial IR allows
the building owner to buy only the report he needs at that
time.
The biggest advantage of aerial infrared
is on roofs that are the most difficult to image from any distance
or angle.
Roofs that, for instance, have a lot of ballast, are covered
with reflective coatings or for whatever reason are impossible
to image while standing on the roof. With high-resolution,
plan view aerial imagery, slight nuances of temperature can
be seen from far enough away to actually see the pattern of
heat and make a determination of where the problems are.
CONCLUSIONS
Every day millions of square feet of perfectly
good roofing materials are disposed of in our landfills.
Why? Because roofs
are often replaced because know one knows where exactly the
roof is damaged until it is too late. If you want your roof
to last, it must be regularly maintained by professionals.
Infrared roof moisture surveying is the best method of non-destructive
testing on roofs, and aerial infrared is the best platform
for performing infrared roof moisture surveys. Improvements
in IR cameras and flight methodology, aerial infrared thermography
and aerial infrared reports are getting better and more useable
everyday.
Author Biography
Gregory R. Stockton is President of Stockton Infrared Thermographic
Services, Inc. Based near Greensboro, NC; the corporation
has six divisions (http://www.stocktoninfrared.com). The
aerial division, AITscan, operates ten aircraft, based coast-to-coast
(http://www.aitscan.com). Greg has twenty-five years experience
in the construction industry, specializing in facilities
construction, maintenance and energy-related technologies.
He has performed infrared thermography since 1989 and has
published fourteen white papers and numerous articles on
infrared thermography.
|